Air source heat pumps
WPL Plus Pack 4 – Technical Data
-
Technical data
Energy efficiency class, heat pump W35
A++
Energy efficiency class, heat pump W55
A++
Energy efficiency class, composite system (heat pump + controller) W35
A+++
Energy efficiency class, composite system (heat pump + controller) W55
A++
Heating output at A7/W35 (EN 14511)
8.00 kW
Heating output at A2/W35 (EN 14511)
8.33 kW
Heating output at A-7/W35 (EN 14511)
12.86 kW
COP at A7/W35 (EN 14511)
4.82
COP at A2/W35 (EN 14511)
4.14
COP at A-7/W35 (EN 14511)
2.98
SCOP (EN 14825)
4.39
Sound power level (EN 12102)
55 dB(A)
Min./max. application limits for heat source
-20-40 °C
Max. application limit on the heating side
65 °C
Height
1045 mm
Width
1490 mm
Depth
593 mm
Weight
175 kg
Rated voltage, compressor
230 V
Rated voltage, emergency/auxiliary heater
230 V
Refrigerant
R410A
Further information about the set contents can be found under the respective product.